FAQ’s
Error: “Warning aaBootstrap ImpersonateUser failed(0x8000401a). ArchestrA Admin user has not be
ISSUE:
Remote Deploy fails with “Warning aaBootstrap ImpersonateUser failed(0x8000401a). ArchestrA Admin user has not been setup or machine is shutting down.”
CAUSE:
The problem is in the Active Directory security policy settings. If the policy is configured to not allow local administrators to run as a system service, this problem will present itself.
RESOLUTION:
Remove the restriction for this group policy. The policy should not be active. Refer to legacy Tech Alert 60 “Impersonate User Failed” Error Message in Logger When Using IAS 2.0 on Active Directory Networks.
Connection to service has not been established ArchestrA IDE will shut down
SR NUMBER:
10418678
ISSUE:
Galaxy create fails with an error Connection to service has not been established. ArchestrA IDE will shut down. Galaxy is created but is
incomplete (failed to create Default ASB Service Instances) and the IDE connection terminates.
CAUSE:
Third party conflict is interfering with the NetTcpPortSharing. For example: There is a known conflict with the Siemens Simulator software (Simit 9.1) where the issue is due to security configuration changes by the SIMIT Virtual Controller installation.
RESOLUTION:
Uninstall the conflicting software then reboot. Consider using the third party software on a separate machine as a workaround.
Does Historian version 17 support multi tier replication?
SR NUMBER:
192113377
ANSWER:
Yes, Historian version 17 Update 3 SP1 and higher support multi-tier replication. Here are important notes:
1. You can only replicate summary data from Tier1 to Tier2, then from Tier 2 to Tier3 and so on it must be simple replication
2. Tier 1 source tag names must be preserved.
3. Tier 1 server name must be preserved.
Errors Establishing Encrypted Suitelink Communications
ANSWER:
Various errors can be encountered when attempting to establish encrypted SuiteLink connections using System Management Server certificates:
WWSLS – Encrypted SuiteLink connection cannot be established.
Problem: Unable to access the required certificate necessary to establish an encrypted SuiteLink connection.
Possible Reason: Expected certificate not found or invalid.
WWSLS ![Multi-Line Message] – Encrypted SuiteLink connection cannot be established.
Problem: Encrypted SuiteLink connection attempt to/from node timed out
Possible Reason: Network interruption or congestion.
WWSLS ![Multi-Line Message] – Encrypted inbound SuiteLink connections are not possible in this configuration.
Problem: Unable to access the required certificate necessary to establish an encrypted SuiteLink connection.
Reason: The application account does not have the required permission to access the certificate.
Contact your support representative and request Hotfix L00154078..
Which version of Application Server corresponds with the CDI version listed in the _GalaxyInfo.txt of a .cab?
SR NUMBER:
24515713
ANSWER:
[IAS 2.1]
2.1 Release: 2559.1144.0.0
2.1 P01: 2559.1144.66.12
2.1 P02: 2559.1144.77.14
[WAS 3.0]
3.0 Release: 2859.1293.0.0
3.0 P01: 2859.1293.24.2
3.0 P02: 2859.1293.53.4
3.0 P03: 2859.1293.70.5
3.0 SP1: 2859.1293.95.15
3.0 SP2: 2859.1293.239.40
[WAS 3.1]
3.1 Release: 3132.57.0.0
3.1 SP1: 3132.57.24.6
3.1 SP2: 3132.57.91.24
3.1 SP2 P01: 3132.57.103.28
3.1 SP3: 3132.57.119.34
3.1 SP3 P01: 3132.57.160.38
[ASP 2012]
3.5 Release: 3275.0113.0000.0000
3.5 P01: 3275.113.110.8
[ASP 2012 R2]
3.6: 3388.0127.0000.0000
3.6 P01: 3388.0127.0126.0006
3.6 P02: 3388.0127.0212.0011
3.6 P03: 3388.0127.0300.0012
[WSP 2014]
4.0: 3509.0148.0000.0000
4.0 P01: 3509.0148.0140.0007
[WSP 2014R2]
4.1 Release: 3735.0233.0000.0000
4.1 P01: 3735.0233.0223.0032
4.1 SP1: 3735.0233.0399.0061
4.1 SP1P1: 3735.0233.0399.0061
4.1 SP1P2: 3735.0233.0776.0085
[WSP 2017]
17.0: 4148.0279.0000.0000
17.1: 4545.0291.0000.0000
17.2: 5019.0376.0000.0000
17.3: 5543.0474.0000.0000
It is important to note that while there are lots of things to contemplate once you’re within the process of deciding on the ideal expert letter writing support, one particular point to keep in your mind is the simple fact that not all of professional correspondence writing companies may offer you with what you need
Correspondence type s and the ideal letter examples readily available that will help companies reach out to potential clients from around the whole world. With today’s technologies, all these correspondence producing services are at present able to create a correspondence for almost any business requirement. Here are some of the Common letter examples that you Ought to Look for when you are assignment writing service in the process of Pick the Best letter writing support to your own needs: